Megger TTR310 Three-Phase Transformer Turns Ratio Test Set

Get Rental Quote Get Sales Quote

The Megger TTR310 measures transformer turns ratio, excitation current and phase deviation for commissioning and maintenance checks.

SKU: 1255 Categories: ,

Description

The Megger TTR310 measures transformer turns ratio, excitation current and phase deviation for commissioning and maintenance checks.

An integrated text-based display and keypad support standalone setup, stored results and comparison with nameplate ratios. Automatic phase selection reduces reconnection work on three-phase transformers. RS-232 transfer supports external reporting; an external printer is optional. This page covers the original TTR310 model.

Key Specifications

  • Turns-ratio range: 0.8:1–45,000:1, excitation dependent
  • Excitation voltage: 8, 40 or 80 V AC
  • Ratio accuracy example: ±0.1% from 0.8:1 to 2,000:1
  • Excitation-current measurement: 0–500 mA
  • Interface: Text LCD and keypad
  • Data transfer: RS-232

Request a rental or sales quote to confirm availability, configuration and included accessories.